ARM55D-000开关量端子板日本横河YOKOGAWA一般规格书

更新时间:2021-06-16 点击量:865

ARM55D-000开关量端子板日本横河YOKOGAWA一般规格书

 

接线端子板   重量2.6公斤

Mechanical Relay Boards Contact Output

 

1、技术指标:

作用形式: 机械式继电器隔离输入
内部连接形式:IDC  50P  两组  可单一或冗余输出
输入信号: ON:≤150Ω;OFF:≥200KΩ
现场连接形式: M3.5螺钉带透明盖板端子块四组,端子块可整体带线拔插
内部电源供电: 24VDC 0.32A,带LED指示和过流、过压、反接保护
现场电源供电: 双路(每16点为一路)24VDC,每路大0.3A,带LED指示和过流、过压、反接保护
回路指示: LED动作指示
绝缘电阻:小10MΩ(500VDC
环境温度和湿度: 0~50℃,10~90%RH
安装尺寸:M5M6螺钉*4  468*51mm18"*2"
尺寸:482mm*111mm(宽19"2.5U
重量:1.4Kg

 

2、配套DCS卡件表:

ADV151  配套电缆: AKB331
ADV161  
配套电缆: AKB337

 

ARM55D-000开关量端子板日本横河YOKOGAWA一般规格书

 

Models

ARM55D

ARM55W ARM55T with switch

ARM55C

 

 

Usage

 

Mechanical Relay DryContact Output (“acontact NO))

Single / Dual-redundant

Mechanical Relay WetContact Output Single /Dual-redundant AUTO/OFF/ON switch onlyfor ARM55T

Mechanical Relay

Dry Contack Output

(“a contact or b contact NO or

NC))

Single / Dual-redun or dant)(*6

Contact Points

32-point

32-point

32-point

Terminals for Field Device

Connection

 

M4 screws

 

M4 screws

M3.5 screws *5

M4 in power input part

 

Modules

ADV551 DO: 32-point

ATD5A Terminal blockADV561 DO: 64-point)(*1

ADV551 DO: 32-point

ATD5A Terminal blockADV561 DO: 64-point)(*1

ADV551 DO: 32-point

ATD5A Terminal blockADV561 DO: 64-point)(*1

 

Signal Cables

AKB331 for 32-pointAKB337 for 64-point

AKB331 for 32-pointAKB337 for 64-point

AKB331 for 32-pointAKB337 for 64-point

 

Maximum Load *2

250 V AC: 2 A per point

30 V DC: 2 A per point

125 V DC: 0.1 A per point *3

250 V AC: 0.6 A per point

30 V DC: 0.6 A per point

125 V DC: 0.1 A per point *3

 

30 V DC: 1.5 A per point

Minimum Load

V, 10 mA

V, 10 mA

V, 10 mA

Power Supply Voltage and Current Consumption of Internal Circuit requireexternal power supply

 

24 V DC Max.0.65 A

 

24 V DC Max.0.65 A

 

24 V DC Max.0.85 A

 

Power Supply for Field

Device

require external powersupply

 

 

-

Dual-line supply power per 16-point

250 V AC: Max. 9.6 A

30 V DC: Max. 9.6 A

125 V DC: Max. 1.6 A

 

 

-

Insulation Resistance

At least 10 MΩ (500 V DC

At least 10 MΩ (500 V DC

At least 10 MΩ (500 V DC

 

 

Withstanding Voltage

Between ?eld device terminalsand cases: 2 kV

Between 24 V power terminals and cases: 500 V

Between 24 V power terminals and ?eld device terminals: 2 kV

Between ?eld device terminalsand cases: 2 kV

Between 24 V power terminals and cases: 500 V

Between 24 V power terminals and ?eld device terminals: 2 kV

Between ?eld device terminalsand cases: 2 kV

Between 24 V power terminals and cases: 500 V

Between 24 V power terminals and ?eld device terminals: 2 kV

Ambient Temperature and

Humidity

 

0 to 50 °C, 10 to 90 %RH

 

0 to 50 °C, 10 to 90 %RH

 

0 to 50 °C, 10 to 90 %RH

 

Standards

Safety Standard [CSA] *3EMC standards [CE Marking], [C-Tick Marking], [KC Marking]

Safety Standard [CSA] *3EMC standards [CE Marking], [C-Tick Marking], [KC Marking]

EMC standards [CE Marking], [C-Tick Marking], [KC Marking]*4

Size

W: 482.6 mm x H: 132.5 mm 3U

W: 482.6 mm x H: 177 mm 4U

W: 482.6 mm x H: 132.5 mm 3U

Weight